Skip to product information
1 of 2

OMRON

OMRON - Relay - G2R-2-S AC100V

OMRON - Relay - G2R-2-S AC100V

Regular price $7.36
Regular price Sale price $7.36
Sale Sold out

📌 General-purpose Relay – 2-Pole, Plug-in Terminal, LED Indicator, Latching Lever

🔧 General Specifications

  • Contact Form: DPDT (Double Pole Double Throw)

  • Contact Method: Single

  • Contact Material: Silver Alloy (Ag alloy)

  • Operating Mechanism: Plug-in terminal with mechanical operation indicator & LED

  • Mounting Method: Socket

  • Applicable Sockets: P2RFZ-08, P2RFZ-08-E, P2RF-08-PU, P2R-08P, P2R-087P, P2R-08A

  • Degree of Protection: Closed type (covered)


âš¡ Electrical Ratings

  • Coil Voltage Ratings:

    • 100 VAC / 50 Hz → 12 mA

    • 100 VAC / 60 Hz → 10 mA

    • 110 VAC / 60 Hz → 11.6 mA

  • Coil Resistance: 4655 Ω

  • Operate Voltage: Max. 80% of rated voltage

  • Release Voltage: Min. 30% of rated voltage

  • Max. Coil Voltage: 110%

  • Power Consumption: Approx. 0.9 VA (60 Hz)


🔌 Contact Ratings

  • Resistive Load:

    • 250 VAC: 5 A

    • 30 VDC: 5 A

  • Inductive Load:

    • 250 VAC: 2 A (cosφ = 0.4)

    • 30 VDC: 3 A (L/R = 7 ms)

  • Max Contact Voltage: 380 VAC / 125 VDC

  • Max Contact Current: 5 A (AC/DC)

  • Max Switching Power:

    • 1250 VA (Resistive)

    • 500 VA (Inductive)

    • 150 W (Resistive)

    • 90 W (Inductive)


🧪 Performance

  • Contact Resistance: Max. 100 mΩ (5 VDC, 1 A)

  • Operate Time: Max. 15 ms

  • Release Time: Max. 15 ms

  • Max Operating Frequency:

    • Mechanical: 18,000 operations/hour

    • Electrical (rated load): 1,800 operations/hour

  • Mechanical Endurance: Min. 10 million operations

  • Electrical Endurance: Min. 100,000 operations

  • Failure Rate: 10 mA at 5 VDC (120 ops/min)


🧯 Safety & Environmental

  • Insulation Resistance: ≥1000 MΩ (500 VDC)

  • Dielectric Strength:

    • Coil ↔ Contacts: 5000 VAC, 1 min

    • Contacts (same polarity): 1000 VAC, 1 min

    • Contacts (different polarity): 3000 VAC, 1 min

  • Vibration Resistance:

    • Destruction: 10–55 Hz, 1.5 mm (double amplitude)

    • Malfunction: Same

  • Shock Resistance:

    • Destruction: 1000 m/s²

    • Malfunction: 200 m/s² (energized), 100 m/s² (not energized)

  • Operating Temperature: -40 to +70 °C (no freezing/condensation)

  • Operating Humidity: 5–85% RH

  • Weight: Approx. 20 g

Made to order – ships from Japan. Lead time: 2+ weeks.